Mitsubishi Electric · FR-D700 Inverter
The reset signal (RES signal) is ON, causing the inverter to immediately shut off its output. This indicates that a reset command has been issued, either manually through a control signal or automatically by the system, placing the inverter in a non-operational state.
Click steps to track your progress.
Inspect the wiring to the RES terminal on the inverter's control terminal block for any shorts or damage.
Verify the status of the external reset command source (e.g., PLC output, physical button) using a multimeter to confirm it is OFF.
Temporarily disconnect the wire from the RES terminal and observe if the inverter powers on without the reset error.
Check the inverter's event log for recurring faults that might automatically trigger a reset (e.g., overcurrent, overvoltage).
Cycle power to the inverter and then re-enable the external reset signal, if applicable, to test its functionality.