Mitsubishi Electric · FR-D700 Inverter
Parameter setting has been attempted in External or NET operation mode when Pr. 77 Parameter write selection is not '2', or when the command source is not the operation panel. This error prevents parameter changes under specific operating mode constraints, aiming to maintain system stability and prevent unintended modifications.
Click steps to track your progress.
Access Pr. 77 (Parameter write selection) and set it to '2' (Write enabled from any source) to allow parameter writing from any source (PU, external terminals, or network).
Verify the current operation mode selected by Pr. 79 (Operation mode selection) to confirm it aligns with the intended control method (e.g., '0' for PU, '1' for External, '3' for NET).
If writing from the operation panel, ensure Pr. 79 is set to '0' (PU operation) or Pr. 77 is set to '2'.
If writing from an external source (e.g., PLC via network), confirm the external device has control authority in the current mode and Pr. 77 is set to '2'.
Re-attempt the parameter write operation after confirming the operation mode and write selection parameter (Pr. 77) are correctly configured.