Mitsubishi Electric · FR-D700 Inverter
The inverter has failed to restart within the set number of retries after a preceding error or trip. This indicates a persistent underlying problem that the inverter's automatic recovery attempts could not resolve, requiring manual intervention to prevent further issues.
Click steps to track your progress.
Identify and resolve the initial fault code that triggered the retries (check fault history, e.g., Pr. 093, Pr. 094).
Reduce the number of autorestart attempts (Pr. 136) to 0 or a low value for diagnostic purposes.
Increase the autorestart delay time (Pr. 137) to allow more time for system recovery between attempts.
Inspect the mechanical load for any binding or issues that would prevent a smooth restart (e.g., manually rotate the shaft).
Monitor the incoming power supply voltage for stability and transient events using a power quality analyzer.