2450H

Module major error

Mitsubishi Electric · MELSEC iQ-R Series

What does 2450H mean?

A critical error has occurred within a module. This error indicates a serious condition that significantly impacts module functionality, and the "Critical" setting is configured to stop the CPU. If the "Direct change setting" is enabled, the system might continue operation without stopping, but the error itself will persist.

Common Causes

  • The "CPU Module Operation Setting at Error Detected Critical" parameter is set to "Stop" under "I/O Assignment Setting".
  • A critical fault condition occurred in an I/O assigned module.
  • A module was physically removed or experienced a failure during operation while "Direct change setting" was enabled.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Verify the "Direct change setting" parameter at [Parameter] -> Module model name -> [CPU Parameter] -> "RAS Setting" -> "Online module change setting".

  2. 2

    Check the "CPU Module Operation Setting at Error Detected Critical" parameter setting within System Parameter -> I/O Assignment Setting (each module).

  3. 3

    Before removing a module, ensure the external power supply input to the module is shut off.

Browse all codes in this manual (9)
Verified technical data. Last updated: April 2026

Related Faults

1200HModule moderate error2400HModule verification error2401HModule verification error
Source: Mitsubishi Electric MELSEC iQ-R Series
Open Manual (Page 45)Search more codes in this manual