EL
ErrorLib
Brands
||
  1. Home
  2. Mitsubishi Electric
  3. FR-A800 Variable Speed Drive (Separated Converter)
  4. E.ECT
About·Privacy·Terms

ErrorLib — Industrial Fault Code Library

Disclaimer: ErrorLib is an independent technical reference tool. While we aim for accuracy, always verify with the manufacturer’s official service manuals before performing maintenance on industrial equipment. ErrorLib is not affiliated with the brands listed.

Feedback·Support ErrorLib
E.ECT

Signal loss detection

Mitsubishi Electric · FR-A800 Variable Speed Drive (Separated Converter)

What does E.ECT mean?

This fault indicates that a critical input signal required for the FR-A800/A800 Plus Series drive's operation has been lost or is not present. This can relate to control signals or feedback, leading to the drive's protective shutoff.

Common Causes

  • Loss of a critical input signal (e.g., run command, enable signal) due to a wiring fault or external control system issue.
  • Sensor or feedback device failure if configured to stop the drive on signal loss.
  • Parameter setting for signal loss detection (e.g., a 'watchdog' parameter for an input) is too sensitive or incorrectly configured.
  • Faulty connections at the control circuit terminal block.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Verify the integrity of all control input wiring, especially for critical signals like RES, OH, or any assigned via Pr.178 (Output terminal function selection).

  2. 2

    Check the external control system (e.g., PLC, HMI) that provides the input signals to the FR-A800/A800 Plus Series drive for proper operation.

  3. 3

    Review parameter settings related to signal loss detection or specific input monitoring (refer to the detailed manual for relevant parameters).

  4. 4

    Measure the voltage at the respective control circuit terminals to confirm the presence of expected signals (e.g., 24VDC for ON state).

  5. 5

    Inspect the control circuit terminal block on the drive for loose connections or physical damage.

Browse all codes in this manual (46)
Verified technical data. Last updated: April 2026

Related Faults

ALM4Output Short-Circuit DetectionE. 1Option FaultE. 13Internal Circuit Fault
Source: Mitsubishi Electric FR-A800 Variable Speed Drive (Separated Converter)
Open Manual (Page 60)Search more codes in this manual