EL
ErrorLib
Brands
||
  1. Home
  2. Mitsubishi Electric
  3. FR-A800 Variable Speed Drive (Separated Converter)
  4. E.EP
About·Privacy·Terms

ErrorLib — Industrial Fault Code Library

Disclaimer: ErrorLib is an independent technical reference tool. While we aim for accuracy, always verify with the manufacturer’s official service manuals before performing maintenance on industrial equipment. ErrorLib is not affiliated with the brands listed.

Feedback·Support ErrorLib
E.EP

Encoder phase fault

Mitsubishi Electric · FR-A800 Variable Speed Drive (Separated Converter)

What does E.EP mean?

This fault indicates an issue with the phase sequence or signal integrity of the encoder feedback connected to the FR-A800/A800 Plus Series drive. It signifies that the drive cannot properly interpret the motor's position or speed from the encoder, often due to incorrect wiring or a damaged encoder.

Common Causes

  • Incorrect wiring or reversed phases of the encoder feedback signals (A, B, Z phases).
  • Damaged encoder cable or loose connections at the drive or encoder end.
  • Faulty encoder (e.g., internal damage, signal corruption, or contamination).
  • Incorrect encoder type or resolution settings in the drive parameters.
  • Excessive electrical noise interfering with the encoder signals.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Verify the encoder wiring at both the FR-A800/A800 Plus Series drive and the encoder itself, ensuring correct phase connections (A, B, Z) and shield termination.

  2. 2

    Inspect the encoder cable for any physical damage, breaks, or signs of insulation wear that could cause signal loss or cross-talk.

  3. 3

    Check the encoder parameters in the FR-A800/A800 Plus Series drive, ensuring the correct encoder type, pulse count (resolution), and signal format are selected.

  4. 4

    Use an oscilloscope to verify the integrity and correct phasing of the encoder A and B signals at the drive terminals while the motor is slowly rotated.

  5. 5

    Ensure proper grounding and shielding practices are followed for the encoder cable to minimize electrical noise interference.

Browse all codes in this manual (46)
Verified technical data. Last updated: April 2026

Related Faults

ALM4Output Short-Circuit DetectionE. 1Option FaultE. 13Internal Circuit Fault
Source: Mitsubishi Electric FR-A800 Variable Speed Drive (Separated Converter)
Open Manual (Page 60)Search more codes in this manual