EL
ErrorLib
Brands
||
  1. Home
  2. Mitsubishi Electric
  3. FR-A800 Variable Speed Drive (Separated Converter)
  4. E.LCI
About·Privacy·Terms

ErrorLib — Industrial Fault Code Library

Disclaimer: ErrorLib is an independent technical reference tool. While we aim for accuracy, always verify with the manufacturer’s official service manuals before performing maintenance on industrial equipment. ErrorLib is not affiliated with the brands listed.

Feedback·Support ErrorLib
E.LCI

4 mA Input Fault

Mitsubishi Electric · FR-A800 Variable Speed Drive (Separated Converter)

What does E.LCI mean?

This fault specifically indicates an issue with a 4-20mA analog current input signal. The fault typically triggers if the input current drops below 4mA (e.g., 0mA), indicating a broken wire or sensor failure.

Common Causes

  • Open circuit or broken wire in the 4-20mA analog input loop to the FR-A800 (e.g., terminal 4 or 5).
  • Failure of the external sensor or transducer providing the 4-20mA signal.
  • Incorrect wiring (e.g., polarity reversal) or loose connections in the current loop.
  • Input current falling below the fault detection threshold (typically 4mA or slightly below) due to a sensor or wiring issue.
  • Internal fault with the FR-A800's 4-20mA input circuit.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Verify the wiring of the 4-20mA input signal to the FR-A800 (e.g., terminals 4, 5) for secure connections and continuity.

  2. 2

    Measure the current in the 4-20mA loop at the FR-A800 terminals using an ammeter to confirm the signal presence and value.

  3. 3

    Check the external sensor or transducer that generates the 4-20mA signal for proper operation and power supply.

  4. 4

    Inspect the current loop wiring for any breaks, shorts, or high resistance connections.

  5. 5

    Ensure that the analog input parameter settings in the FR-A800 (e.g., Pr.59 for analog input selection, scaling parameters) are correctly configured for 4-20mA input.

Browse all codes in this manual (46)
Verified technical data. Last updated: April 2026

Related Faults

ALM4Output Short-Circuit DetectionE. 1Option FaultE. 13Internal Circuit Fault
Source: Mitsubishi Electric FR-A800 Variable Speed Drive (Separated Converter)
Open Manual (Page 102)Search more codes in this manual