EL
ErrorLib
Brands
||
  1. Home
  2. Mitsubishi Electric
  3. FR-A800 Variable Speed Drive (Separated Converter)
  4. E.OD
About·Privacy·Terms

ErrorLib — Industrial Fault Code Library

Disclaimer: ErrorLib is an independent technical reference tool. While we aim for accuracy, always verify with the manufacturer’s official service manuals before performing maintenance on industrial equipment. ErrorLib is not affiliated with the brands listed.

Feedback·Support ErrorLib
E.OD

Excessive position fault

Mitsubishi Electric · FR-A800 Variable Speed Drive (Separated Converter)

What does E.OD mean?

This fault occurs when the actual position deviation in the FR-A800/A800 Plus Series drive exceeds the permitted threshold, typically in applications requiring precise position control with a feedback device. This indicates a failure to maintain the commanded position.

Common Causes

  • Incorrect position control parameters (e.g., position loop gains, following error limits) tuned for the mechanical system.
  • Mechanical issues such as binding, excessive backlash, a disconnected load, or excessive friction.
  • Faulty or misaligned position feedback device (e.g., encoder, resolver) or its wiring.
  • Motor not responding adequately to position commands (e.g., undersized motor, motor fault, or insufficient torque).
  • Rapid or unrealistic position commands from the external controller.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Verify all position control parameters, including position loop gains and following error limits, are correctly tuned for the mechanical system and application.

  2. 2

    Inspect the mechanical system for any binding, excessive friction, backlash, or disconnection between the motor and the load.

  3. 3

    Check the position feedback device (e.g., encoder) for proper operation, secure mounting, and signal integrity. Verify wiring to the FR-A800/A800 Plus Series drive.

  4. 4

    Monitor the commanded position and actual position feedback through the drive's display or FR Configurator2 to assess the deviation.

  5. 5

    Reduce the commanded acceleration/deceleration rates or velocity limits from the external controller to determine if the fault can be avoided.

Browse all codes in this manual (46)
Verified technical data. Last updated: April 2026

Related Faults

ALM4Output Short-Circuit DetectionE. 1Option FaultE. 13Internal Circuit Fault
Source: Mitsubishi Electric FR-A800 Variable Speed Drive (Separated Converter)
Open Manual (Page 60)Search more codes in this manual