EL
ErrorLib
Brands
||
  1. Home
  2. Mitsubishi Electric
  3. FR-A800 Variable Speed Drive (Separated Converter)
  4. E.OS
About·Privacy·Terms

ErrorLib — Industrial Fault Code Library

Disclaimer: ErrorLib is an independent technical reference tool. While we aim for accuracy, always verify with the manufacturer’s official service manuals before performing maintenance on industrial equipment. ErrorLib is not affiliated with the brands listed.

Feedback·Support ErrorLib
E.OS

Overspeed occurrence

Mitsubishi Electric · FR-A800 Variable Speed Drive (Separated Converter)

What does E.OS mean?

This fault indicates that the motor speed has exceeded the programmed overspeed detection level in the FR-A800/A800 Plus Series drive. This protective function prevents uncontrolled acceleration or runaway conditions of the motor.

Common Causes

  • Motor or load inertia driven by external forces (e.g., regenerative load, gravity) causing speed to exceed the commanded value.
  • Overspeed detection level parameter set too low for the application.
  • Faulty speed feedback (e.g., encoder reading incorrectly high or inconsistent).
  • FR-A800/A800 Plus Series drive losing control of the motor due to incorrect parameters or improper tuning.
  • Brake failure or insufficient braking capacity on a vertical or overhauling application.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Verify the overspeed detection level parameter is correctly set above the maximum expected operating speed but below the motor's absolute maximum safe speed.

  2. 2

    Check for external forces acting on the motor/load that could cause overspeed, such as regenerative loads or gravity, and ensure adequate braking or regeneration capacity.

  3. 3

    If an encoder is used for speed feedback, verify its functionality and wiring for accurate speed measurement.

  4. 4

    Review other speed control parameters (e.g., PID gains, acceleration/deceleration times) to ensure stable operation and prevent speed overshoot.

  5. 5

    In applications with external forces, ensure any mechanical brakes or external braking systems are fully functional and properly sized.

Browse all codes in this manual (46)
Verified technical data. Last updated: April 2026

Related Faults

ALM4Output Short-Circuit DetectionE. 1Option FaultE. 13Internal Circuit Fault
Source: Mitsubishi Electric FR-A800 Variable Speed Drive (Separated Converter)
Open Manual (Page 60)Search more codes in this manual