Mitsubishi Electric · FR-A800 Variable Speed Drive (Separated Converter)
This fault indicates an issue with the non-volatile memory on the control circuit board of the FR-A800/A800 Plus Series drive, where drive parameters are stored. This can lead to loss of settings or an inability to store new parameters, affecting drive operation.
Click steps to track your progress.
Attempt to re-initialize the parameters to default settings and then carefully re-enter all necessary application-specific parameters.
Verify the stability of the control power supply (e.g., 24VDC at terminal +24).
Try to upload parameters from the FR-A800/A800 Plus Series drive using FR Configurator2, and if successful, download a known good parameter set.
Inspect the control circuit board for any visible damage or signs of overheating.
If the fault persists after re-parameterization and power cycling, it may indicate an internal hardware failure of the control circuit board, requiring replacement.