Mitsubishi Electric · FR-A800 Variable Speed Drive (Separated Converter)
This fault indicates an issue with the feedback signal or control in the FR-A800's internal PID control loop. This prevents the inverter from accurately regulating a process variable based on the PID controller.
Click steps to track your progress.
Verify the wiring of the PID feedback sensor to the FR-A800 for secure connections and continuity.
Measure the PID feedback signal (voltage or current) at the FR-A800 terminals to ensure it is stable and within the expected range.
Check the external sensor providing the PID feedback for proper operation, calibration, and power supply.
Review the PID-related parameters in the FR-A800 (e.g., Pr.130-Pr.132 for feedback input, Pr.133-Pr.136 for PID gains, Pr.139 for PID fault detection) to ensure correct configuration.
If the feedback signal appears correct, try adjusting the PID gains to improve stability, or temporarily disable PID fault detection (if applicable) for diagnosis.