L2 Open Phase, 51CM Connector Open, or Input Circuit Fault
Mitsubishi Electric · R410A Systems
What does FA mean?
The L2 phase of the power supply is open, or the 51CM connector on the outdoor unit is disconnected. Alternatively, a general fault has occurred in the outdoor unit's input power circuit, potentially due to issues with rectifiers, filters, or other input components.
Common Causes
- Loss of power on phase L2.
- Open circuit at the 51CM connector.
- General input circuit fault impacting power supply.
Repair Steps & Checklist
Click steps to track your progress.
- 1
Measure voltage between L1-L2, L2-L3, and L3-L1 at the outdoor unit main power terminals — expect balanced 3-phase voltage.
- 2
Inspect the 51CM connector on the outdoor unit PCB — verify it is securely seated.
- 3
Check continuity of the wiring connected to the 51CM connector using a multimeter.
- 4
Measure the incoming AC voltage at the outdoor unit's main power terminals.
- 5
Check the fuses or circuit breakers in the input power path to the outdoor unit.