P4
Drain Sensor Abnormal
Mitsubishi Electric · R410A Systems
What does P4 mean?
The indoor unit's drain sensor is abnormal, indicating a fault with its circuit. This sensor monitors the condensate drain pan level to prevent overflow, and a fault can lead to water leakage.
Common Causes
- Drain sensor (22) is abnormal.
- Faulty sensor for drain pan level.
- Wiring issue to the drain sensor.
Repair Steps & Checklist
Click steps to track your progress.
- 1
Measure the resistance or output of the drain sensor according to manufacturer specifications.
- 2
Inspect the sensor's wiring and connector on the indoor unit PCB for damage, corrosion, or secure seating.
- 3
Check the drain pan for actual water level and visually verify float switch operation if applicable.
Verified technical data. Last updated: March 2026