U4

Overheat Protection / Outdoor Thermistor Short/Open

Mitsubishi Electric · R410A Systems

What does U4 mean?

The outdoor unit has activated its overheat protection, indicating that a critical component or the overall unit temperature is too high. This could also be caused by the outdoor ambient thermistor being short-circuited or open-circuited, preventing accurate temperature sensing.

Common Causes

  • Overheat protection activated.
  • Outdoor thermistor (49C) is shorted or open.
  • Excessive temperature detected by outdoor sensor.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Verify outdoor unit fan motor operation and fan blade integrity.

  2. 2

    Ensure the outdoor unit's condenser coil is clean and free of obstructions to airflow.

  3. 3

    Measure the resistance of the outdoor thermistor at its leads — compare to a resistance-temperature chart if available.

  4. 4

    Inspect the thermistor's wiring and connector on the outdoor unit PCB for damage or corrosion.