UE
High Pressure Error (Ball Valve Closed)
Mitsubishi Electric · R410A Systems
What does UE mean?
The system is experiencing high refrigerant pressure, specifically indicating that a ball valve, most likely a service valve in the refrigerant circuit, is closed or partially closed, restricting refrigerant flow.
Common Causes
- High pressure error condition.
- Ball valve in the system is closed.
- Restriction in refrigerant flow causing high pressure.
Repair Steps & Checklist
Click steps to track your progress.
- 1
Inspect all service ball valves (liquid line, suction line) on the outdoor unit — verify they are fully open.
- 2
Measure high-side pressure using manifold gauges after confirming all valves are open.
- 3
Check for any other flow restrictions in the liquid line such as a clogged filter drier.
Verified technical data. Last updated: March 2026