Mitsubishi Electric · Mitsubishi FR-E800 Variable Frequency Drive
This fault indicates a general malfunction within the inverter's internal circuitry. The specific cause is not detailed in the manual, suggesting a fundamental hardware problem that cannot be resolved through basic troubleshooting. Continued attempts to operate with this fault may lead to further damage.
Click steps to track your progress.
Power down the inverter, wait 10 minutes for capacitor discharge, then visually inspect the main control board for burnt components, bulging capacitors, or signs of liquid damage.
Verify the operation of the cooling fan by observing rotation or measuring fan voltage at its terminals (e.g., 24VDC).
Measure the resistance across the DC bus terminals (+/P and -/N) when power is off; an abnormally low reading may indicate an IGBT short.
Check for proper grounding of the inverter chassis (ground resistance < 1 Ohm) to minimize static discharge or surge effects.
Record all parameter settings (e.g., using a parameter copy function if available) before considering a replacement inverter.