Mitsubishi Electric · Mitsubishi FR-E800 Variable Frequency Drive
The inverter output is shut off if an incorrect signal type or magnitude (e.g., 30mA+ current or 7.5V+ voltage) was detected on terminal 2 or 4, contrary to the parameter settings for current input. This indicates a mismatch between the physical input signal and the configured analog input type.
Click steps to track your progress.
1. Measure the actual analog input signal (voltage or current) directly at inverter terminals 2 and 4 using a multimeter.
2. Verify Pr.73 (Terminal 2 input selection) and Pr.267 (Terminal 4 input selection) are set correctly for the incoming signal type (e.g., 0-5V, 0-10V, 4-20mA).
3. Check analog input wiring for correct polarity, shielding, and absence of short circuits to ground or other potentials.
4. Temporarily disconnect the external analog signal source from terminals 2 and 4 and verify the fault clears.
5. If using 4-20mA, measure the current loop to ensure it's not open (expected: 4mA minimum signal).