E.FIN

Heatsink Overheat

Mitsubishi Electric · Mitsubishi FR-E800 Variable Frequency Drive

What does E.FIN mean?

This fault indicates that the inverter's internal heat sink has exceeded its safe operating temperature, triggering a temperature sensor and shutting down the inverter output. This usually happens when the ambient temperature is too high, the heat sink is blocked by debris, or the cooling fan is not functioning correctly. Sustained overheating shortens the lifespan of inverter components and can lead to permanent damage.

Common Causes

  • Inverter cooling fan failure (fan not rotating, obstructed, or worn bearings).
  • High ambient temperature within the control panel enclosure or insufficient enclosure ventilation.
  • Clogged heatsink fins with dust, lint, or debris, impeding airflow.
  • Continuous operation near or above the inverter's rated current (P0-02) for extended periods without adequate cooling.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Verify the inverter's cooling fan is rotating freely and at rated speed; clean fan blades if obstructed by debris.

  2. 2

    Measure ambient temperature inside the control panel enclosure and ensure it is within the inverter's specified operating range (e.g., <40°C).

  3. 3

    Clean inverter heatsink fins thoroughly using compressed air or a soft brush to remove accumulated dust and debris.

  4. 4

    Check for proper air circulation pathways within the control panel and verify enclosure ventilation fans/filters are operational.

  5. 5

    Monitor the inverter output current with a clamp meter during operation and compare it to the inverter's continuous rating (P0-02).

Browse all codes in this manual (55)
Verified technical data. Last updated: April 2026