Mitsubishi Electric · Mitsubishi FR-E800 Variable Frequency Drive
The inverter output is shut off when the load on the motor falls below the defined lower limit fault detection range. This protective function detects abnormally light load conditions, potentially indicating a mechanical issue or a disconnected load, and is active only when Pr.1491 is not '9999'.
Click steps to track your progress.
Check Pr.1487 (Load fault detection function selection) to ensure it is correctly configured for lower limit detection.
Monitor the motor current (e.g., Pr.205 Output current) during operation to identify the actual current at which the fault occurs.
Inspect the mechanical coupling between the motor and the load for breakage or slippage (e.g., visually inspect belt tension).
Verify the process condition (e.g., liquid level in tank, material flow) to confirm the presence of an expected load.
Adjust Pr.1489 (Lower limit warning detection width) to a slightly lower value if the observed minimum load is within safe operating limits.