Mitsubishi Electric · Mitsubishi FR-E800 Variable Frequency Drive
The inverter output is shut off if stall prevention operation causes the output frequency to drop to 0.5 Hz for 3 seconds, or if torque limit operation causes frequency to drop to Pr.865 and output torque exceeds Pr.874 for 3 seconds in speed control. This protective fault indicates severe motor overload or an issue with stall prevention settings.
Click steps to track your progress.
Monitor motor current (e.g., Pr.205 Output current) and torque output (if available) during operation to confirm actual load.
Inspect the mechanical system for any binding, friction, or obstruction that could be overloading the motor.
Increase Pr.22 (Stall prevention operation level) slightly or extend the time delay for stall detection if transient overloads are common.
Verify motor sizing against the application's maximum and continuous load requirements, potentially recommending a larger motor.
Adjust Pr.865 (Stall prevention frequency lower limit) to a slightly lower value if the application legitimately operates below 0.5 Hz under specific conditions.