Mitsubishi Electric · Mitsubishi FR-E800 Variable Frequency Drive
The motor speed has exceeded the configured Pr.374 Overspeed detection level under encoder feedback, Real sensorless vector, Vector, or PM sensorless vector control, leading to an inverter shutdown. This protective function prevents mechanical damage from excessive speed.
Click steps to track your progress.
1. Monitor actual motor speed via the inverter display or monitoring software and compare it to the commanded speed and Pr.374.
2. Increase Pr.374 (Overspeed detection level) by 5-10% above the maximum expected operating speed for the application.
3. Inspect encoder wiring for loose connections or damage, and verify encoder pulse output signal using an oscilloscope (expected: clean A/B/Z phase pulses).
4. Verify parameters Pr.30 (Braking operation frequency) and Pr.70 (Braking duty factor) are correctly configured for any external braking resistor.
5. Check for mechanical free play or excessive load inertia that could cause the motor to overspeed without electrical input.