Mitsubishi Electric · Mitsubishi FR-E800 Variable Frequency Drive
The inverter output is shut off when the motor loses synchronization during operation, a condition specifically monitored under PM sensorless vector control. This fault indicates a loss of control over the motor's rotor position, leading to erratic operation.
Click steps to track your progress.
Perform an autotuning procedure specific to PM motors (e.g., using Pr.1130 and Pr.1131 with Pr.1100 set to 1) to accurately identify motor parameters.
Reduce acceleration/deceleration times (e.g., Pr.7 Accel time, Pr.8 Decel time) to prevent exceeding the motor's dynamic limits.
Monitor actual motor speed (e.g., Pr.206 Output frequency) and current (e.g., Pr.205 Output current) to observe behavior during the step-out event.
Verify the actual load on the motor against its rated torque to ensure it's not consistently overloaded.
Ensure the PM motor's specifications (e.g., poles, flux linkage) are correctly entered into Pr.1130 to Pr.1134.