Mitsubishi Electric · Mitsubishi FR-E800 Variable Frequency Drive
This warning appears when the current load on the inverter deviates from the detection width defined by Pr.1488 (Upper limit warning detection width) or Pr.1489 (Lower limit warning detection width). It indicates an unexpected load condition, either too heavy or too light, potentially due to equipment issues.
Click steps to track your progress.
Monitor motor current (e.g., Pr.205 Output current monitor) and compare it to the expected operating current under normal load.
Inspect the mechanical system (e.g., bearings, belts, gears) for any signs of binding, wear, or obstruction.
Adjust Pr.1488 (Upper limit warning detection width) or Pr.1489 (Lower limit warning detection width) based on actual measured load current during stable operation.
Verify the motor's actual output power against the load demand using a power meter.
Check for unusual noise or vibration from the motor or driven equipment, indicating mechanical issues.