Mitsubishi Electric · Mitsubishi FR-E800 Variable Frequency Drive
This alarm appears when the safety stop function is activated, resulting in the shutoff of the inverter's output. It signifies a protective measure triggered by an emergency stop device or a disconnection within the safety circuit.
Click steps to track your progress.
Verify the state of the external emergency stop device or safety relay contacts (e.g., measure voltage at input terminal STOA/STOB).
Inspect all safety chain devices (e.g., light curtains, door interlocks) for activation or damage.
Check inverter safety input parameter settings (e.g., P3-01 to P3-08) for correct configuration (e.g., Normally Closed, Normally Open).
Reset the safety circuit externally after resolving the trigger condition, then attempt to reset the inverter fault.
Measure continuity across safety input terminals to ensure proper closure or opening as expected by the safety circuit design.