This fault is triggered when the compressor stops three consecutive times within one minute of startup due to overcurrent protection or startup failure protection. It points to significant issues within the outdoor unit's power delivery, compressor, or refrigeration system. Leaving this unresolved risks severe damage to the compressor and other critical components.
Click steps to track your progress.
Disconnect main power to the outdoor unit. Using an insulation resistance tester (Megger), measure the insulation resistance of the compressor motor windings to ground and between phases (U-V, V-W, W-U).
Check the refrigerant charge pressure (e.g., high-side and low-side) using a manifold gauge set. Verify pressures are within the manufacturer's specified operating range for the ambient temperature.
Verify input line voltage (L1-L2, L2-L3, L3-L1) and phase balance using a multimeter at the main power terminals (e.g., TB1) during startup attempt (briefly).
Inspect all compressor power wiring (U, V, W terminals) for tightness, corrosion, or signs of overheating. Ensure proper torque on terminal connections.
Measure the resistance of the compressor motor windings (e.g., U-V, V-W, W-U). Compare to specifications; unequal or open readings indicate internal motor fault.
If external factors are ruled out and compressor windings are good, consider replacing the inverter P.C. board, as its current sensing or drive circuitry may be faulty.