EL
ErrorLib
Brands
||
  1. Home
  2. Omron
  3. MX2 Inverter RS-485 Connection Guide
  4. 1508.5
About·Privacy·Terms

ErrorLib — Industrial Fault Code Library

Disclaimer: ErrorLib is an independent technical reference tool. While we aim for accuracy, always verify with the manufacturer’s official service manuals before performing maintenance on industrial equipment. ErrorLib is not affiliated with the brands listed.

1508.5

Communication Timeout Error

Omron · MX2 Inverter RS-485 Connection Guide

What does 1508.5 mean?

This status bit, when active (1), indicates that the Serial Communication Unit (SCU) did not receive a response from the Destination Device within the expected time frame. This suggests either the Destination Device is not responding, is too slow to reply, or the response message is not reaching the SCU, causing the communication attempt to fail.

Common Causes

  • The Destination Device (inverter) is not powered on or not properly communicating.
  • Incorrect Destination node address configured in the CMND instruction (C+3 lower byte).
  • The response timeout value in the CMND instruction operand (C+5) is set too short for the communication link or device processing time.
  • Loose or damaged serial communication cable connections preventing response reception.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Verify the Destination Device is powered ON and its Modbus slave address matches the CMND instruction's destination node address (C+3 lower byte).

  2. 2

    Increase the Response timeout parameter C+5 (e.g., from #0000 (2s) to a higher value) in the CMND instruction operand to allow sufficient time for the Destination Device to respond.

  3. 3

    Inspect the serial communication cable for continuity and secure connections at both the SCU and the Destination Device.

  4. 4

    Monitor the Destination Device's status to confirm it is not in a busy or non-responsive state that would delay its replies.

Browse all codes in this manual (15)
Verified technical data. Last updated: April 2026

Related Faults

#01Unsupported Function Code#02Invalid Modbus Address#03Invalid Modbus Data Format
Source: Omron MX2 Inverter RS-485 Connection Guide
Open Manual (Page 58)Search more codes in this manual