Omron · NJ/NX-series Machine Automation Controller
A missing serial incremental encoder CTS signal logic error was detected. This fault indicates a problem with the Clear-To-Send (CTS) signal from the encoder, crucial for serial communication with the drive.
Click steps to track your progress.
Inspect the encoder cable for any physical damage, cuts, crimps, or loose insulation, paying particular attention to the integrity of the shielding and strain relief points.
Verify all encoder cable connections at both the encoder side and the Omron NJ/NX controller/drive terminal block/module are secure, clean, and correctly terminated according to the wiring diagram.
Measure the DC supply voltage delivered to the encoder at its input terminals, ensuring it falls within the specified operational voltage range (e.g., 5VDC, 24VDC) as per the encoder's datasheet.
Check the electrical continuity of the dedicated CTS signal line, including its return path or ground reference, from the encoder connector pin to the corresponding input terminal on the Omron NJ/NX controller or its associated encoder interface module.
Verify the encoder communication parameters and interface settings within the Omron NJ/NX controller's Sysmac Studio project, confirming they match the installed encoder's type, resolution, and specified serial communication protocol.