08160000 hex

Phase-Z Connection Error

Omron · NJ/NX-series Machine Automation Controller

What does 08160000 hex mean?

An error such as broken wiring was detected in the external encoder phase-Z connection. This indicates a physical wiring issue with the external encoder's Z-phase signal, impacting its reference position detection.

Common Causes

  • An error such as broken wiring was detected in the external encoder phase-Z connection.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Inspect the entire cable run between the external encoder and the Omron NJ/NX controller for physical damage, wear, and proper termination at both ends.

  2. 2

    Verify the continuity of the Z-phase signal wire, its return path, and shield (if applicable) using a multimeter between the encoder connector and the Omron NJ/NX controller's input terminals.

  3. 3

    Measure the supply voltage at the external encoder's power input terminals to confirm it meets the manufacturer's specified voltage range.

  4. 4

    Check the encoder input parameters within the Omron NJ/NX controller's Sysmac Studio software, ensuring correct Z-phase input settings and encoder type configuration.

  5. 5

    Monitor the Z-phase input status in the Omron NJ/NX controller's diagnostic tools (e.g., I/O monitor) while slowly rotating the encoder to confirm signal detection.