CPU Communication Error
Omron · MX2 Inverter
What does E22 mean?
This fault occurs when there is a communication failure between the two internal CPUs within the inverter. Such a failure prevents coordinated operation and leads to an inverter trip, indicating a critical internal control issue.
Common Causes
- Transient power disturbance or voltage ripple affecting internal CPU power rails (e.g., 5VDC or 3.3VDC).
- Electromagnetic interference (EMI) ingress affecting internal communication buses due to poor grounding or shielding practices.
- Hardware failure of an internal CPU component or communication bus driver chip.
- Firmware corruption on one of the CPUs preventing proper initialization or inter-processor handshake.
- Severe operating conditions (e.g., extreme vibration) causing internal board connection issues.
Repair Steps & Checklist
Click steps to track your progress.
- 1
1. Cycle power to the inverter completely (remove main AC supply for at least 30 seconds), then reapply to reset internal CPUs.
- 2
2. Verify input supply voltage (VAC) stability at the inverter terminals (R, S, T) using a multimeter; check for significant sags or surges.
- 3
3. Inspect inverter grounding connections (PE terminal) for integrity and low impedance (typically <1 Ω to earth ground).
- 4
4. Isolate potential sources of EMI by temporarily disabling adjacent high-frequency switching devices or ensuring proper separation of power and control wiring.
- 5
5. If the error persists after power cycling, consider a firmware re-flash (if supported) or replacement of the inverter's control board.