Otis · DSD 412 DC Elevator Drive
The Loop Contactor auxiliary contact failed to pick up or drop out within the designated time, as requested by the DSD 412 drive. The detection time is set by Function #102, which can be 450ms or 3 seconds.
Click steps to track your progress.
Check for proper feedback at TB1-7 for the Loop Contactor Aux contact.
Check the contactor for an open coil or mechanical binding.
Check the Pilot Relay LPR for defects.
Identify and resolve interference from other elevator relay contact circuits.
If using large contactors with large HP drives, set Function #102 to 1 (On) for a 3-second fault detection time; otherwise, set to 0 (Off) for 450ms.