Otis · DSD 412 DC Elevator Drive
The Counter Electromotive Force (CEMF) of the motor exceeded 109% of the measured AC input voltage to the drive. This is a warning only and does not cause an automatic drive shutdown.
Click steps to track your progress.
Check and correct the 3 Phase Input AC Line Voltage if it is too low.
Verify weak field set point #49 against the desired motor voltage at top speed.
Check and correct motor field control tuning to prevent CEMF overshoot.
Review and verify settings for parameters #49, #50, #51, #52, #54, and #55.