The actual field current is failing to track the field current command by more than F192 (default = 0.05PU) for 5 seconds. This is not a shutdown fault, but a warning.
Click steps to track your progress.
Check AC voltage on AC1 and AC2; it should typically be 1.5 to 2.5 times VACmin where VACmin = VDC/0.9 or (Full Fld Amps * Field resistance)/0.9.
Verify that the drive is using correct self-tune values and/or field response settings.
Monitor F620 (Fld Trkg Diff); it should be less than F192.
Adjust F192 ('F413 Detect Level') to a higher value if necessary, but observe caution prior to doing this.