901

PCU IST FAULT

Otis · DSD 412 DC Elevator Drive

What does 901 mean?

Current flow in excess of 300% of the rated armature current is detected within the armature circuit. This indicates a severe overload, a fault in the motor, or a measurement error.

Common Causes

  • Ground fault or an intermittent connection within the motor armature circuit.
  • Malfunction or failure of the current measuring module.
  • Suboptimal tuning or configuration of the current regulator.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Inspect the motor armature circuit for any ground faults or intermittent connections.

  2. 2

    Test the current measuring module for accurate readings and replace if faulty.

  3. 3

    Review and adjust the current regulator tuning parameters.