909

RIPPLE FAULT

Otis · DSD 412 DC Elevator Drive

What does 909 mean?

Repeated instances of high peak-to-average motor armature current are detected. This condition can be caused by defective hardware, inadequate regulator tuning, or other oscillatory operating conditions.

Common Causes

  • Defective hardware components, which can be diagnosed using the PCU Diagnostics CDU function #998.
  • Poor tuning or configuration of the drive's current regulator.
  • Other conditions leading to oscillatory operation within the motor or drive system.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Execute the PCU Diagnostics CDU function #998 to identify any defective hardware.

  2. 2

    Review and adjust the drive's regulator tuning parameters to stabilize current ripple.