910

BLOWN FUSE FAULT

Otis · DSD 412 DC Elevator Drive

What does 910 mean?

One or more of the three AC line fuses are open. This condition is checked during power-up and can be requested via the PCU F#998 Diagnostics function. Detection is achieved by measurements from voltage dividers on the Armature Interface PCB (A2).

Common Causes

  • One or more of the AC input fuses have blown.
  • A problem with the AC power wiring, such as a loose connection or damage.
  • A faulty DSPR power relay.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Inspect and replace any blown AC input fuses.

  2. 2

    Check all AC power wiring connections for tightness and integrity.

  3. 3

    Test the DSPR power relay for proper operation.

  4. 4

    Utilize the PCU F#998 Diagnostics function to pinpoint which AC line fuse is open.