Otis · DSD 412 DC Elevator Drive
One of the SCRs in the system is not conducting current as expected. This condition is checked only upon request through the PCU #998 Diagnostics CDU function. The optional handheld PCDU will also identify which specific SCR pair is faulty. A DSD Power Down is required.
Click steps to track your progress.
Initiate a DSD Power Down for the drive.
Run the PCU #998 Diagnostics CDU function to identify the non-conducting SCR.
If available, use the optional handheld PCDU to identify the exact open SCR pair.
Check the SCR gating leads for proper connection and integrity.
Replace the identified open SCR.