Otis · DSD 412 DC Elevator Drive
This fault is declared if the number entered for Rated Armature Current (parameter #3) is outside the acceptable range of 0.125 to 2.0 times the bridge current rating, which is determined by the bridge sense resistor on the Cube ID PCB located on the Armature Interface PCB. A DSD power down is required.
Click steps to track your progress.
Enter a value for parameter #3 (Rated Armature Current) that is within 0.125 to 2.0 times the drive's bridge current rating.
Perform a DSD power down after adjusting the parameter.