Otis · DSD 412 DC Elevator Drive
The field bridge rating is determined by a sense resistor on the Field Interface board, selected by SW1, which sets the motor field current feedback scaling for the A/D converter. If this resistance value is not recognized, a Field Sense Fault is declared, indicating a hardware fault on the Field Interface PCB, Drive Control PCB, or interconnecting cables and hardware. A DSD power down is required.
Click steps to track your progress.
Check that connector J13 is properly seated on the Field Interface board.
Verify the integrity of the interconnecting cable for any defects.
Confirm that the correct field sense resistor is selected by SW1 on the Field Interface PCB.
If problems persist, replace the Field Interface PCB or the Drive Control PCB.
Perform a DSD power down after troubleshooting.