Otis · DSD 412 Elevator System
The Counter Electromotive Force (CEMF) of the motor exceeded 118% of the rated VAC input voltage to the drive. This fault causes a drive shutdown to prevent fuse blowing.
Click steps to track your progress.
Measure and correct the 3 Phase Input AC Line Voltage.
Check motor field current setting and field regulator operation.
Adjust velocity regulator to correct excessive drive speed overshoot.
Review and verify settings for parameters #49, #50, #51, #52, #54, and #55 to correct motor field control dynamic tuning.