905

FIELD LOSS FAULT

Otis · DSD 412 Elevator System

What does 905 mean?

The field current feedback has dropped below 80% of the expected current during specific operating conditions: Field Weakening Mode (Top speed, #49), Full Field Mode (Accel or Decel, #50), or Standing Field Mode (not running, #53). This fault will shut down the drive.

Common Causes

  • Open circuit failure of motor field or motor field wiring.
  • Hardware failure of motor field control circuitry.
  • Loss of power or incorrect phasing to the Field Rectifier.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Check the motor field and motor field wiring for an open circuit.

  2. 2

    Inspect motor field control circuitry for hardware failure.

  3. 3

    Verify power supply and phasing to the Field Rectifier.

Browse all codes in this manual (57)