Otis · DSD 412 Elevator System
This fault indicates that the motor field current failed to reach near its rated amperes within 6 seconds during testing. This condition may occur during Self-Tune (Function #997) or Self-Diagnostic (Function #998) routines.
Click steps to track your progress.
Verify motor field current with an independent clamp-on DC ammeter.
Check all motor field connections for continuity and proper installation.
If voltage is insufficient, reconnect the field windings for lower voltage (and higher current) or provide a step-up transformer for the motor field circuit.
Ensure that the proper current tap at A3TB4 is used, calibration switch A3S1 is set correctly, and adjustments #49, #50, #52, and #55 are accurate.
Replace the faulty SCR/Rectifier power module for the motor field.