The DSD 412 drive will not perform Self-Tune if the calculated load inductance is less than 170 micro-henries. This fault may occur during Self-Tune (Function #997) or Self-Diagnostic (Function #998).
Click steps to track your progress.
Verify the actual armature inductance of the motor to confirm it is not below 170 micro-henries.
Verify that the Vac value set in parameter #9 is correct for the input line voltage.
Manually enter the minimum allowed inductance value into parameter #5 if the actual inductance cannot be increased.
Set parameter #2 to OFF if performing manual entry for inductance.