This fault occurs when the motor generates excessive regenerative energy back into the drive controller's DC bus during rapid deceleration or when driving an overhauling load (e.g., lowering a weight). This rapid increase in DC bus voltage can exceed safe limits and damage the drive's internal components if not dissipated properly.
Click steps to track your progress.
Increase the deceleration ramp time (Parameter P1-04) by 1-2 seconds and retest the application.
Measure the resistance of the external braking resistor with a multimeter (power OFF). Compare to its specified value.
Verify the braking chopper is functioning by measuring voltage across the braking resistor during deceleration (if safely possible).
If an overhauling load is present, confirm the braking resistor and chopper are correctly sized for the application's regenerative energy.
Ensure overvoltage trip level (Parameter P5-02) is at its default or appropriate setting (if configurable for specific applications).