Schneider Electric · Altivar Machine ATV340 Programming
This fault occurs when communication is lost between the drive controller and its connected serial devices, such as a remote keypad display or a MODBUS master controller. This prevents external control, monitoring, or parameter adjustment of the drive, interrupting automated processes. The cause could be physical disconnection, incorrect settings, or device malfunction.
Click steps to track your progress.
Verify physical communication cable integrity (e.g., check for cuts, bends) and ensure all connectors are securely seated.
Confirm all communication parameters (e.g., P6-01 baud rate, P6-02 parity, P6-03 drive address) match the master device settings precisely.
Check for proper termination resistors (e.g., 120 Ohm for RS-485) at both physical ends of the communication bus.
Measure communication signal levels (e.g., using an oscilloscope for RS-485) to detect noise or signal degradation.
Temporarily disconnect other devices from the communication bus to isolate potential address conflicts or faulty devices.