This fault occurs during the auto-tuning process, indicating that the drive controller is unable to successfully tune itself to the connected motor. This is typically due to using a specialized motor or one whose power rating does not match the 'n' (nominal) or 'nld' (no-load) settings of the UFb parameter, preventing optimal motor control. Incorrect tuning can lead to inefficient operation or other motor control issues.
Click steps to track your progress.
Verify all motor nameplate data (P2-01, P2-02, P2-03, P2-04, P2-05) matches the drive's parameter settings precisely.
Disconnect motor power cables (U, V, W) from the drive output terminals (T1, T2, T3) and perform a winding resistance test. Check for open phases.
Ensure no external devices (contactors, fuses, filters) are connected between the drive output and the motor during the tuning process.
Review the motor cable length. For long cable runs, consider using a drive-side line reactor or specific drive parameters for compensation.
If using a specialized motor, review the drive manual for specific tuning procedures or consider disabling autotuning and manually entering motor parameters.