Schneider Electric · XW Pro NA Operation Guide
This Escalating Automatic Fault indicates an AC over-voltage shutdown (above 135 V). If it occurs 3 times in 30 seconds, it becomes a manual fault, meaning the inverter has repeatedly shut down to protect connected loads.
Click steps to track your progress.
Measure AC output voltage at inverter terminals L1, L2, L3 (or L1, N) using a true RMS multimeter under no-load and full-load conditions.
Verify inverter output voltage configuration (e.g., Parameter P3-10, P3-11) is set correctly for the application's nominal voltage (e.g., 120V or 240V).
Check for regenerative load conditions and verify proper functioning of braking resistors or regeneration units (e.g., measure resistance of braking resistor).
Monitor utility grid voltage at the inverter input terminals (L1, L2, L3, N) to confirm it remains below 135V nominal.
Perform a factory reset of inverter parameters (e.g., Parameter P0-01 to "Reset") and reconfigure essential settings to eliminate configuration errors.