Schneider Electric · XW Pro NA Operation Guide
This Manual Fault indicates that an unidentified transfer relay is faulty, or an external AC source was incorrectly wired directly to the AC output. This can lead to improper power transfer and potential damage to the inverter.
Click steps to track your progress.
De-energize all AC inputs and outputs, then individually test continuity across each internal transfer relay's contacts with the inverter off.
Perform a thorough visual inspection of all AC input and output wiring connections for any signs of miswiring or external AC source backfeeding.
Verify the integrity of all external AC circuit breakers and contactors to ensure they are opening correctly and not shorted.
Measure output current on all AC phases (L1, L2, L3) using a clamp meter under operational conditions to identify any sustained overcurrent.
Check system log data for correlation with previous fault conditions that might indicate which relay was active during overcurrent or transfer events.