Schneider Electric · XW Pro NA Operation Guide
This Automatic Fault occurs due to an over-frequency anti-islanding condition, detected when the AC frequency exceeds qualification limits. The inverter stops selling power and disconnects from the grid to ensure safety and regulatory compliance.
Click steps to track your progress.
Measure utility grid frequency at the inverter's AC input terminals (L1, L2, L3) using a power quality analyzer to verify grid stability.
Verify anti-islanding frequency thresholds configured in the inverter (e.g., Parameter P4-05, P4-06) against local utility requirements.
Check all external grid connection points and switchgear for loose connections or arcing that could generate electrical noise affecting frequency measurement.
Perform an inverter self-test or calibration routine if available, to verify the accuracy of its internal frequency measurement circuit.
Temporarily disable anti-islanding protection (if allowed by local regulations and safe to do so for testing) to determine if the fault clears.