Schneider Electric · XW Pro NA Operation Guide
This fault indicates an under-frequency condition detected by the anti-islanding protection, exceeding the AC qualification limits. This mechanism ensures the inverter disconnects from the grid if grid power is unstable or absent, preventing dangerous backfeeding and potential damage to equipment.
Click steps to track your progress.
1. Measure the actual grid frequency at the inverter's AC input terminals (e.g., using a power quality analyzer like a Fluke 435 Series II) and compare it to the inverter's displayed frequency.
2. Verify the anti-islanding under-frequency trip setting in the inverter's parameters (e.g., Parameter G1-03) and ensure it matches local grid codes.
3. Check for any recent large load changes or disturbances on the local electrical grid that could explain a frequency sag.
4. Power cycle the inverter to reset its internal frequency measurement circuits and clear any transient conditions.