Schneider Electric · XW Pro NA Operation Guide
This fault indicates an L1 over-voltage condition (135 VAC) detected by the anti-islanding protection, triggering a fast disconnect. This mechanism ensures the inverter disconnects from an unstable grid, protecting both the inverter and grid from potential damage due to excessive voltage.
Click steps to track your progress.
Using a true RMS multimeter, measure and record the L1-Neutral voltage at the inverter's AC input terminal L1 over several minutes, looking for spikes.
Compare measured L1-Neutral voltage values to the specified 135 VAC trip threshold and the inverter's P_AI_L1_Volt_Fast parameter.
Inspect the wiring connection for the L1 phase and neutral conductor at the inverter's input terminals for looseness or damage.
Review the inverter's event log for occurrences of high L1 voltage readings that correlate with fault triggers.
If grid conditions appear stable and parameters are correct, perform a diagnostic check on the inverter's internal L1 voltage sensing circuit or contact service.